CONV. HORN AND STROBE, د اخلي SYS-HS-UL

System Sensor selectable output horns, strobes, and horn strobes are rich with features guaranteed to reduce installation times and maximize profits.

التفاصيل

Features
• Mounting plate included for compatibility with a wide range of back box sizes
• Three field selectable candela settings: 15, 75, and 115
• Easy to use rotary dials for selection of candela and horn settings
• Built in synchronization feature keeps strobes in sync for up to 30 minutes
• Strobes Listed to UL 1638; Horns Listed to UL 464
• Horn settings on the horn strobe model include high and low volume, continuous or temporal 3 tone
• Round trim ring available for ceiling mount applications
• Universal Fire symbol is language independent
• Trim plate allows mini horn to mount to a variety of backboxes and fit aesthetically with the horn strobe and strobe

The System Sensor line of notification devices offers the most
flexibile and easy-to-use line of horns, strobes, and horn strobes in the industry. With red housing, universal fire symbol and a ceiling mount accessory available these devices can meet virtually any application. They also mount to a wide variety of back box sizes to offer the most flexibility in installation.

This line of devices features a wide variety of features that simplifies installations. The mounting plate allows the devices to be compatible with a wide range of back box sizes. Settings for the strobe and horn are done using easy to set rotary switches on the back of the device. Synchronization is achieved without the use of additional modules; when powered with a filtered DC source, the strobe portion is capable of self synchronization for 30 minutes per NFPA 72.

Devices work on 24 volts DC or full wave rectified power. Three candela options are available for the strobe. On the horn strobe model, high and low volume are options for the horn as well as a continuous tone or temporal 3 output. The mini horn model has a continuous tone output and one volume setting.

Available accessories include a round trim ring to adapt the wall device for ceiling mount applications. Simply install the round ring over the square device for a perfect fit on the ceiling. An adapter plate is also available for the mini horn. It fits to a wider range of back boxes and fits with the family look of the horn strobe and strobe devices.

 

Architect/Engineer Specifications
General
System Sensor strobe and horn strobes shall mount to a 2″x4″, 4″x4″, single-gang, double-gang, 4″ Octagon, 105mm x 105mm, 65mm round, 86mm x 86 mm, 60mm x 60mm back box. System Sensor devices shall be powered from a non-coded notification appliance circuit output and shall operate on a nominal 24 volts. 24-volt-rated notification appliance circuit outputs shall operate between 17 and 33 volts. Devices operate between 32 and 120 degrees Fahrenheit from a regulated DC or full-wave rectified unfiltered power supply. Strobes and horn strobes shall have field-selectable candela settings including 15, 75 and 115 cd. The devices shall not operate on a coded power supply. Horn – strobe and strobe devices shall have built-in synchronization capability. Upon initial power up the devices shall be synchronized for up to 30 minutes.

Strobe
The strobe shall be a System Sensor Model SYS-ST or SYS-STR listed to UL 1638 and shall be approved for fire protective service. The strobe shall be wired as a primary-signaling notification appliance flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system.

Horn Strobe Combination
The horn strobe shall be a System Sensor Model _______ listed to UL 1638 and UL 464 and shall be approved for fire protective service. The horn strobe shall be wired as a primary-signaling notification appliance and comply with the Americans with Disabilities Act requirements for visible signaling appliances, flashing at 1 Hz over the strobe’s entire operating voltage range. The strobe light shall consist of a xenon flash tube and associated lens/reflector system. The horn shall have two audibility options and an option to switch between a temporal three-pattern and a non-temporal (continuous) pattern. These options are set by a multiple position switch.

Mini Horn
The mini horn shall mount to a single-gang back box. With the accessory trim plate it shall mount to a 2″x4″, 4″x4″, single-gang, double-gang, 105mm × 150mm, 65mm round, 86mm × 86mm, 60mm × 60mm back box. The mini horn shall provide a continuous tone output.