Addressable Fire Alarm Control panel 1 loop IFS 7002-1

Interactive Fire Control Panel IFS 7002 is an up-to-date, high reliable, multi-functional and versatile device, providing the user with unexpected potential in the design, installation and operation of addressable fire alarm systems.

Description

PRODUCT DESCRIPTION

Interactive Fire Control Panel IFS 7002 is an up-to-date, high reliable, multi-functional and versatile device, providing the user with unexpected potential in the design, installation and operation of addressable fire alarm systems.

TECHNICAL DATA:

Physical configuration:
– 1 fire alarm loops
– 2 monitored outputs
– 1 relay outputs for fire condition
– 1 programmable relay outputs for fire condition
– 1 relay output for fault conditions

Fire alarm zones:
– Maximum number of zones – 64
– Maximum number of fire detectors and in-out devices – 60

Fire alarm loops:
– Maximum number of fire detectors in a loop – 125
– Connecting line – two-wire shielded
– Maximum resistance of a loop – 100
– Output resistance of a loop – 20
– Maximum consumption of a loop – 200mA

Monitored outputs: – 2 pcs
– Type – potential
– Еlectrical characteristics – (24±5)V/0,5A

Relay output for fire conditions – 1 pc
– Type – potential free, switching
– Electrical characteristics – 3A/125VAC; 3A/30VDC

Relay (programmable) output for fire conditions – 1 pc
– Type – potential free, switching
– Electrical characteristics – 3A/125VAC; 3A/30VDC

Relay output for fault conditions – 1 pc
– Type – potential free, switching
– Electrical characteristics – 3A/125VAC; 3A/30VDC

Performance:
– Control over fire alarm loops and monitored outputs for fault conditions (short circuit and interruption) and automatic reset
– Dedicated led indication per fire zone
– Detection of removed devices in the loops and automatic reset
– Ability to set the zones in Coincidence Mode
– Two phases of Fire condition, programmable time for Fire condition stage I, separately for each zone
– Option to prolong the time period for Fire condition stage I with programmable inspection period, specified for each zone
– Built-in sounder for fire condition – one tonal, discontinuous, can be switched off
– Built-in sounder for fault condition – one tonal, discontinuous, can be switched off
– Built-in real time clock
– Set of test modes and options for adjustment

– Setting the clock:
– Check ups on light and sound indications
– Test of fire alarm zones
– Adjustment of outputs and integrated external devices
– Programming of parameters and modes of operation
– Remote programming of the parameters from distant operator control point

– Energy independent event log of registered events with the events type, date and hour – up to 1023 events
– Interfaces for communication with external devices – CAN 2.0B and USB.

Indications of registered events:
– Light indication – LED
– Text messages – LCD display, 320 х 240 points, backlit
– Sound signaling – built-in sounder

Power supply:
Mains:
– voltage – 220/230V
– frequency – 50Hz

Back up batteries:
– battery type – lead, gel electrolyte
– number of batteries – 2 pcs
– connection – serial connection
– nominal voltage of the back up battery – 2x12V DC
– nominal capacity C20 – 7Ah
– charge voltage – 28V

Consumption on back up batteries supply:
– at 24V – <160mA
– at 26V – < 150mA

Power supply to external devices:
– Voltage – (24±5)V
– Maximum current value (including current of monitored outputs) – 1А

Dimensions:
– Overall dimensions – 286 x 148 x 125 mm
– Weight (batteries not included) – 1.240 kg.

Share this product

Related Products